  • High Temp Cut-Off for use with all BROAN powered attic ventilators

    • Limit switch automatically turns off ventilator at 204° F
    • Includes manual on/off switch
  • (4 Questions : 5 Answers)

    Product Q&A

    Ask your questions. Share your answers.

     
     
    « Back
     
     
    be adjusted down to 130 or 140 F?
    I'm looking for something that will give me confidence that the 353 ventilator will shut down automatically at a max temperature that I can set as low as 130 or 140 F for automatic shut OFF, and that I can set at 90F to turn the fan ON.
    Age: 35-44
     
    Products related to my question
     
     
     
     
    1 year, 2 months ago
    Customer avatar
    by
    RB1
    Hartford, CT
    0points
    0out of 0found this question helpful.
    Was this helpful?helpful0unhelpful0

    Answers

    Answer: 
    Thank you for your question on the model 353 attic ventilator. The 353 comes with a user settable thermostat to turn the fan on and off. It has a range of 75 – 135 degrees Fahrenheit. A normal setting would be around 110 degrees Fahrenheit. We also have a model 73, high temperature cut off that can be used with this fan. It will cut off the power to the fan if it gets to 204 degrees Fahrenheit. The model 73 cannot be adjusted. It is factory set at 204 degrees.
    1 year, 2 months ago
    Customer avatar
    by
    Read all my Q&A
     
    Please wait while more information about BroanCustomerService is loaded.
    Additional information about BroanCustomerService could not be loaded.
    +1point
    1out of 1found this answer helpful.
    Was this helpful?helpful1unhelpful0

    Answer: 
    Thank you for your question on the model 353 attic ventilator. The 353 comes with a user settable thermostat to turn the fan on and off. It has a range of 75 – 135 degrees Fahrenheit. A normal setting would be around 110 degrees Fahrenheit. Instructions for setting the thermostat are found in the Installation guide. We also have a model 73, high temperature cut off that can be used with this fan. It will cut off the power to the fan if it gets to 204 degrees Fahrenheit. The model 73 cannot be adjusted. It is factory set at 204 degrees. For further assistance, please contact our Technical Support department at 800-637-1453.
    1 year, 1 month ago
    Customer avatar
    by
    Read all my Q&A
     
    Please wait while more information about BroanCustomerService is loaded.
    Additional information about BroanCustomerService could not be loaded.
    0points
    0out of 0found this answer helpful.
    Was this helpful?helpful0unhelpful0
    Has staff answer
     
    1 answer

    how low can the temp be set

    1 year, 5 months ago
    Customer avatar
    by
    jeff
    0points
    0out of 0found this question helpful.
    Was this helpful?helpful0unhelpful0

    Answers

    Answer: 
    Thank you for your interest in our attic fans. The thermostats on the attic fans are adjustable up to 130 degrees. The lowest setting is 70 degrees
    1 year, 5 months ago
    Customer avatar
    by
    Read all my Q&A
     
    Please wait while more information about BroanCustomerService is loaded.
    Additional information about BroanCustomerService could not be loaded.
    0points
    0out of 0found this answer helpful.
    Was this helpful?helpful0unhelpful0
    I need two attic ventilation fans for the size of my attic. So I want to know if both can be wired to the same control.
    1 year, 2 months ago
    Customer avatar
    by
    dragon
    California, USA
    0points
    0out of 0found this question helpful.
    Was this helpful?helpful0unhelpful0

    Answers

    Answer: 
    Thank you for your question on the model 73 high temperature cut off switch. The model 73 can be used for multiple fans, as long as the total current does not exceed the current limit of the switch. The 73 is rated at 22 Amps. For further assistance, please contact our Technical Support department at 800-637-1453.
    1 year, 1 month ago
    Customer avatar
    by
    Read all my Q&A
     
    Please wait while more information about BroanCustomerService is loaded.
    Additional information about BroanCustomerService could not be loaded.
    0points
    0out of 0found this answer helpful.
    Was this helpful?helpful0unhelpful0
    Has staff answer
     
    1 answer

    Does this bypass the 355BK thermostat?

    I'm going to install a 355BK attic fan and need to remotely control the thermostat from a wall switch in the garage. How does this affect the built in thermostat? Is there special wiring requirements?
    Age: 45-54
    Gender: Male
    7 months ago
    Customer avatar
    by
    Rob
    Springdale, AR, USA
    0points
    0out of 0found this question helpful.
    Was this helpful?helpful0unhelpful0

    Answers

    Answer: 
    Thank you for your question on the model 355BK attic ventilator. We do not have an option to remotely control the thermostat on this model. The model 73 is a high temperature cut off to disconnect the power from a fan if the ambient temperature goes over 204 degrees Fahrenheit. Please contact the Technical Service Department at 800-637-1453 for further assistance.
    7 months ago
    Customer avatar
    by
    Read all my Q&A
     
    Please wait while more information about BroanCustomerService is loaded.
    Additional information about BroanCustomerService could not be loaded.
    0points
    0out of 0found this answer helpful.
    Was this helpful?helpful0unhelpful0
    1 of 1
    1 of 1